Copper busbar current rating table (DIN 43671)
The values most often used in switchgear and busbar design: continuous current rating, cross-section and weight per metre for rectangular copper busbars (copper flat bar), single bar.
Conditions: E-Cu (Cu-ETP) copper, single bar, alternating current (up to 60 Hz), indoors, ambient temperature 35 °C, busbar temperature 65 °C, bar on edge. Weights are calculated from the nominal cross-section at 8.9 kg/dm³.
| Size (mm) | Cross-section (mm²) | Weight (kg/m) | Bare busbar (A) | Painted busbar (A) |
|---|---|---|---|---|
| 12 × 2 | 24 | 0.214 | 108 | 123 |
| 15 × 2 | 30 | 0.267 | 128 | 148 |
| 15 × 3 | 45 | 0.401 | 162 | 187 |
| 20 × 2 | 40 | 0.356 | 162 | 189 |
| 20 × 3 | 60 | 0.534 | 204 | 237 |
| 20 × 5 | 100 | 0.890 | 274 | 319 |
| 20 × 10 | 200 | 1.780 | 427 | 497 |
| 25 × 3 | 75 | 0.667 | 245 | 287 |
| 25 × 5 | 125 | 1.113 | 327 | 384 |
| 30 × 3 | 90 | 0.801 | 285 | 337 |
| 30 × 5 | 150 | 1.335 | 379 | 447 |
| 30 × 10 | 300 | 2.670 | 573 | 676 |
| 40 × 3 | 120 | 1.068 | 366 | 435 |
| 40 × 5 | 200 | 1.780 | 482 | 573 |
| 40 × 10 | 400 | 3.560 | 715 | 850 |
| 50 × 5 | 250 | 2.225 | 583 | 697 |
| 50 × 10 | 500 | 4.450 | 852 | 1,020 |
| 60 × 5 | 300 | 2.670 | 688 | 826 |
| 60 × 10 | 600 | 5.340 | 985 | 1,180 |
| 80 × 5 | 400 | 3.560 | 885 | 1,070 |
| 80 × 10 | 800 | 7.120 | 1,240 | 1,500 |
| 100 × 5 | 500 | 4.450 | 1,080 | 1,300 |
| 100 × 10 | 1,000 | 8.900 | 1,490 | 1,810 |
| 120 × 10 | 1,200 | 10.680 | 1,740 | 2,110 |
| 160 × 10 | 1,600 | 14.240 | 2,220 | 2,700 |
| 200 × 10 | 2,000 | 17.800 | 2,690 | 3,290 |
How to read the table
- Painted busbars dissipate heat better and carry more current than bare bars of the same size.
- Parallel bars: with several bars per phase the currents do not simply add up; use the multi-bar tables of the standard.
- Other ambient temperatures: above 35 °C or in closed, unventilated enclosures the ratings drop and correction factors apply.
- Direct current (DC): without skin effect, DC ratings are somewhat higher than AC ratings for large sections.
This table is for preliminary selection and information. Final busbar size must be set by a qualified engineer, taking short-circuit withstand, voltage drop and enclosure conditions into account.
Sources
Values are based on DIN 43671 (Copper busbars; continuous current ratings) and compiled by cross-checking Rittal technical data and Ampac load tables; both sources list identical values.
Related pages
Frequently asked questions
How many amps does a 40×10 copper busbar carry?
Based on DIN 43671, a single 40×10 mm copper busbar at 35 °C ambient carries about 715 A bare and about 850 A painted (AC, continuous).
Why do painted busbars carry more current?
A painted surface radiates heat better, so the bar stays cooler and can carry more current within the same temperature limit.
How is copper busbar weight calculated?
Width (mm) × thickness (mm) × 8.9 ÷ 1,000 gives the weight per metre in kg. A 40×10 mm bar weighs about 3.56 kg/m.
Do these values apply to medium-voltage switchgear?
They are continuous ratings based on temperature rise. For medium voltage, insulation, short-circuit and enclosure conditions must also be considered.